Cabur short-circuitable test terminal blocks (MCM and MCT series) are essential electrical safety devices installed between measurement transformers (CT/VT) and fiscal electricity meters.

They allow technicians to inject calibration signals, measure secondary currents, and replace meters without interrupting the primary circuit and without opening the current transformer secondary windings (preventing lethal overvoltages).

Manufactured with high-dielectric self-extinguishing polyamides and gold-plated test sockets, they are certified according to EN 60947-7-1 and fiscal customs sealing requirements.

Key Strengths

Safe CT Secondary Short-Circuiting

Eliminates dangerous overvoltages during meter maintenance.

Customs Sealing Provision

Compliant with customs and utility fiscal anti-tamper requirements.

Integrated Test Sockets

Direct connection for reference standard instruments and calibrators.

High Insulation Voltage

Rated up to 1000V AC/DC according to EN 60947-7-1.

Modular Cabur Architecture

DIN rail mounting with MCM2/3 and MCT series.

Technical Specifications & Parameters

Electrical
Insulation Voltage Ui
1000 V AC / DC
Rated Impulse Voltage Uimp
8 kV
Rated Current In
41 A / 57 A
Mechanical & Environmental
Connecting Capacity
0.5 – 10 mm² flexible / rigid conductors
Insulating Material
Polyamide UL94 V-0 self-extinguishing
Specifications
Standards & Compliance
EN 60947-7-1, CEI 0-16 fiscal sealing specifications